Underground Residential Distribution (URD) Cable Engineering Guide: Primary 15kV–35kV Concentric Neutral vs Secondary 600V Direct Burial Sizing, TR-XLPE Insulation & Standards (ICEA S-94-649, AEIC CS8, ASTM B231)
Underground Residential Distribution (URD) Cable Engineering Guide: Primary 15kV–35kV Concentric Neutral vs Secondary 600V Direct Burial Sizing, TR-XLPE Insulation & Standards (ICEA S-94-649, AEIC CS8, ASTM B231)
This engineering guide covers Underground Residential Distribution (URD) cable design, 15kV-35kV primary sizing, and 600V direct burial standards.
Modern municipal developments, residential subdivisions, and suburban commercial parks overwhelmingly mandate underground utility infrastructure to eliminate the visual clutter, severe storm vulnerabilities, and high maintenance costs of traditional overhead distribution lines. At the heart of this grid architecture lies Underground Residential Distribution (URD) cabling, comprising two distinct yet interdependent electrical layers: medium-voltage (MV) primary cables (5kV to 35kV) that feed pad-mounted distribution transformers in underground loops, and low-voltage (LV) secondary multiplex cables (600V) that deliver split-phase 120/240V power directly from transformer terminals into residential meter bases.
Designing, specifying, and deploying URD cable infrastructure requires rigorous adherence to electrical and mechanical standards. Because these cables operate directly buried in soil or pulled into submerged polyvinyl chloride (PVC) and high-density polyethylene (HDPE) conduits, they endure continuous moisture exposure, cyclic thermal loading, earth settling stresses, and aggressive soil chemical environments. This technical guide delivers an authoritative analysis of primary concentric neutral URD cables versus secondary 600V direct burial multiplexed assemblies, examining dielectric material physics (Tree-Retardant Cross-Linked Polyethylene vs. Ethylene Propylene Rubber), concentric neutral sizing paradigms (100% full neutral vs. 1/3 neutral), trenching mechanics, termination practices, and international manufacturing standards under ANSI/ICEA S-94-649, AEIC CS8, ASTM B231, and ICEA S-105-692.
URD Grid Architecture: Primary MV Loops and Secondary Service Drops
Underground Residential Distribution topologies differ fundamentally from overhead radial distribution. In typical North American and international suburban developments, utility distribution substations step transmission or sub-transmission voltages down to medium-voltage distribution levels—most commonly 15kV (12.47kV, 13.2kV, or 13.8kV), 25kV (24.94kV), or 35kV (34.5kV phase-to-phase).
The primary circuit originates at a circuit breaker or recloser on an overhead-to-underground transition pole (riser pole) equipped with medium-voltage lightning arresters and fused cutouts. From the riser, the primary URD cable descends through a protective conduit into an underground trench, forming an open-loop primary distribution circuit that interconnects a series of pad-mounted single-phase or three-phase distribution transformers. Under normal operating conditions, one transformer switch in the loop remains open (the "normal open point"). If a primary cable fault occurs, maintenance crews can isolate the faulted cable segment and re-energize all connected transformers from the alternate feed, minimizing customer outage duration.
At each pad-mounted transformer, the primary voltage is stepped down to 120/240V single-phase (for typical residential homes) or 208Y/120V / 480Y/277V three-phase (for light commercial and multifamily facilities). Secondary URD multiplex cables (duplex, triplex, or quadruplex) connect directly to the low-voltage secondary bushings of the transformer and extend underground through private property easements to the electric meter socket. Specifying the correct high-reliability underground cable solutions across both primary and secondary circuits is vital to achieving a 40- to 50-year maintenance-free asset lifespan.
Primary URD Cable Construction, Dielectric Physics, and Materials
Primary URD cables must withstand high continuous electrical stress, transient switching surges, lightning impulses, and aggressive wet underground environments without dielectric breakdown. The industry standard construction is defined by ANSI/ICEA S-94-649 and AEIC CS8, utilizing a multi-layer coaxial architecture engineered through single-pass triple extrusion.
Conductor Engineering (Phase Core)
The primary conductor carries the medium-voltage phase current. While soft-annealed bare copper conductors (per ASTM B3 and ASTM B8) are utilized in compact urban vaults where duct cross-sectional area is constrained, the overwhelming majority of URD projects specify Class B compressed or compact stranded aluminum alloy 1350-H19 per ASTM B230 and ASTM B231. Aluminum provides a superior strength-to-weight ratio and approximately 61% the electrical conductivity of copper at a fraction of the raw material cost, significantly reducing overall project capital expenditures. Conductor stranding is compressed to reduce outside diameter and fill strand interstices, and strand-filling compounds (water-blocking mastic or powder) are frequently incorporated to prevent longitudinal water migration in the event of outer sheath puncture.
Triple-Extruded Insulation System
The core insulation system comprises three distinct layers extruded simultaneously in a true continuous vulcanization (CCV) line under dry nitrogen pressure: 1. Conductor Shield (Inner Semiconductive Screen): A black, cross-linkable thermosetting semiconducting compound extruded directly over the aluminum strands. This layer provides a perfectly cylindrical, smooth equipotential surface, eliminating electric field stress concentrations caused by individual strand contours and preventing micro-void formation at the conductor-dielectric boundary. 2. Primary Dielectric Insulation (TR-XLPE vs. EPR): - Tree-Retardant Cross-Linked Polyethylene (TR-XLPE): Developed to eliminate the catastrophic water-treeing degradation that caused premature failures in first-generation standard XLPE cables in the 1970s and 1980s. Modern TR-XLPE incorporates advanced chemical additives that inhibit electrochemical water tree growth under alternating electric fields and moisture penetration. It provides exceptionally low dielectric losses (dissipation factor tan delta < 0.0004), high dielectric breakdown strength (>30 kV/mm), and an impulse withstand voltage (BIL) of 95kV (15kV class) to 200kV (35kV class) at continuous operating temperatures of 90°C and emergency overload ratings of 130°C. - Ethylene Propylene Rubber (EPR): Formulated from elastomeric terpolymers, EPR offers inherent resistance to water treeing and superior mechanical flexibility, making it popular in cold-weather climates and tight pad-mounted transformer cabinets. However, EPR exhibits higher dielectric loss (tan delta approximately 0.003 - 0.005) and greater charging currents, making TR-XLPE the primary choice for utility-scale efficiency. 3. Insulation Shield (Outer Semiconductive Screen): A free-stripping extruded thermosetting semiconductive layer bonded to the outer surface of the insulation. Per AEIC CS8, the stripping tension must remain controlled between 3 to 24 lbf (13 to 107 N) at a 90-degree pull angle, allowing cable jointers to cleanly strip the shield during elbow termination installation without gouging the underlying primary insulation.
Concentric Neutral Shield
Unlike three-phase tape-shielded or wire-shielded industrial power cable systems installed in dry industrial raceways, primary URD cable utilizes a concentric neutral consisting of multiple solid, annealed bare round copper wires helically applied directly over the outer semiconductive shield. The concentric neutral serves two critical engineering functions: it confines the electric field symmetrically within the cable insulation (preventing external radial capacitive discharge), and it provides a continuous, low-impedance metallic path for single-phase return current and system ground-fault clearing currents. For specialized overhead-to-underground interfaces and high-density distribution layouts, engineers frequently cross-reference our concentric cable range to match neutral cross-sectional conductance with upstream substation protective relays.
Protective Outer Jacket
While unjacketed primary URD cables were common in early installations, bare concentric copper wires suffered widespread electrochemical corrosion and galvanic degradation from dissolved soil salts, fertilizers, and stray direct currents. Modern primary URD cables universally mandate an encapsulating or insulating outer jacket: - Insulating Linear Low-Density Polyethylene (LLDPE): Extruded tightly over the concentric neutral wires. LLDPE provides exceptional moisture impermeability, high puncture resistance, low coefficient of friction for conduit pulling, and complete electrical isolation of the neutral from corrosive soil chemicals. - Semi-Conductive Polyethylene: Used by specific utilities to maintain continuous radial ground contact along the cable length while providing mechanical wear protection.
Concentric Neutral Sizing Rules: Full 100% vs. One-Third (33.3%) Neutral
A critical specification decision in primary URD cable engineering is the geometric and ampacity sizing of the concentric neutral conductor. The two standard configurations are:
- Full 100% Neutral (One-to-One Current Capacity):
- In single-phase residential loop circuits, the concentric neutral conductor carries the entire return load current of the phase conductor back to the substation neutral bus.
- Therefore, the total cross-sectional area of the spiraled copper neutral wires must equal the full electrical conductivity of the aluminum phase core.
- For example, a 1/0 AWG aluminum primary cable typically utilizes sixteen #14 AWG solid bare copper neutral wires, providing equivalent phase ampacity and robust short-circuit current carrying capability during phase-to-ground flashovers.
- One-Third (33.3%) Neutral:
- In balanced three-phase primary trunk feeders, the vector sum of balanced three-phase load currents at the neutral point theoretically equals zero. The neutral only carries unbalance currents and triplen harmonic components.
- Specifying a 1/3 neutral significantly reduces cable weight, outside diameter, and raw copper material costs while maintaining sufficient thermal capacity to safely clear phase-to-ground faults via substation fast-trip breakers.
- For example, a 1000 kcmil aluminum primary feeder typically utilizes twenty-six #10 AWG or twenty #9 AWG copper neutral wires, engineered precisely to handle ground fault current duration without melting or thermal sheath damage.
Secondary 600V URD Multiplex Cables: Direct Burial Architecture
Once primary voltage is stepped down at the pad-mounted transformer, secondary 600V URD multiplex cables distribute power to individual residences. These cables operate in harsh direct-burial conditions without concrete encasement and must provide decades of mechanical robustness and electrical isolation.
Multiplexed Construction Typologies
- Duplex Secondary URD: One insulated phase conductor twisted together with one bare or covered neutral conductor. Used for street lighting circuits and dedicated 120V residential auxiliary services.
- Triplex Secondary URD: Two insulated phase conductors twisted around a bare or yellow-extruded neutral conductor. This is the dominant cable type in North American residential electrification, delivering 120/240V three-wire single-phase service to single-family homes.
- Quadruplex Secondary URD: Three insulated phase conductors twisted around one neutral conductor. Utilized for 208Y/120V or 480Y/277V three-phase commercial strip malls, apartment complexes, and agricultural pumping facilities.
Conductor and Insulation Standards
Secondary phase conductors are manufactured from compact or compressed 1350-H19 aluminum or AA-8000 series aluminum alloy per ASTM B800 and ASTM B801. Phase conductors are insulated with high-grade, heavy-wall black cross-linked polyethylene (XLPE) rated for 90°C wet and dry conditions per ANSI/ICEA S-105-692 and UL 854 (USE-2 type). The insulation provides superior resistance to mechanical abrasion, stone impingement, moisture absorption, and sunlight exposure during transformer cabinet risers.
The neutral conductor in Triplex and Quadruplex assemblies can be specified as bare aluminum 1350-H19, full-size insulated aluminum with a distinctive yellow extruded jacket, or black XLPE with three continuous co-extruded longitudinal yellow identification stripes to ensure rapid, unambiguous visual identification in unlit distribution handholes and trenches.
Engineering Technical Specifications and Parameter Comparison
To assist utility distribution planners, EPC contractors, and procurement engineers, the following tables detail physical dimensions, electrical ratings, and insulation criteria across primary and secondary URD product families manufactured at SiTong Cable.
Table 1: Primary 15kV URD Cable Dimensions and Concentric Neutral Sizing (175 Mil TR-XLPE, 100% Insulation Level)
| Conductor Size (AWG / kcmil) | Conductor Material | Insulation Thickness (mils / mm) | Concentric Neutral Configuration (Count x AWG) | Approx. Core OD (mm) | Approx. Overall Cable OD (mm) | Approx. Net Weight (kg/km) | Direct Burial Ampacity (90°C, RHO=90) |
|---|---|---|---|---|---|---|---|
| #2 AWG | Compact Aluminum | 175 mil / 4.45 mm | 10 x #14 AWG Solid Cu (Full) | 18.2 mm | 24.8 mm | 685 kg/km | 155 A |
| 1/0 AWG | Compressed Aluminum | 175 mil / 4.45 mm | 16 x #14 AWG Solid Cu (Full) | 20.3 mm | 27.2 mm | 875 kg/km | 200 A |
| 2/0 AWG | Compressed Aluminum | 175 mil / 4.45 mm | 20 x #14 AWG Solid Cu (Full) | 21.6 mm | 28.7 mm | 1,020 kg/km | 225 A |
| 4/0 AWG | Compressed Aluminum | 175 mil / 4.45 mm | 16 x #12 AWG Solid Cu (Full) | 25.1 mm | 32.5 mm | 1,410 kg/km | 290 A |
| 250 kcmil | Compressed Aluminum | 175 mil / 4.45 mm | 13 x #12 AWG Solid Cu (1/3) | 26.8 mm | 33.8 mm | 1,320 kg/km | 320 A |
| 500 kcmil | Compressed Aluminum | 175 mil / 4.45 mm | 16 x #10 AWG Solid Cu (1/3) | 33.8 mm | 41.5 mm | 2,180 kg/km | 465 A |
| 750 kcmil | Compressed Aluminum | 175 mil / 4.45 mm | 15 x #9 AWG Solid Cu (1/3) | 39.2 mm | 47.4 mm | 2,980 kg/km | 570 A |
| 1000 kcmil | Compressed Aluminum | 175 mil / 4.45 mm | 20 x #9 AWG Solid Cu (1/3) | 43.6 mm | 52.2 mm | 3,750 kg/km | 655 A |
Notes: Dimensions conform to ANSI/ICEA S-94-649. Ampacities calculated per IEEE 835 / Neher-McGrath method assuming 90°C conductor temperature, 20°C ambient earth temperature, and soil thermal resistivity of 90 K-cm/W.
Table 2: Primary vs. Secondary URD Engineering Comparison Matrix
| Engineering Feature | Primary MV URD Cable | Secondary 600V URD Multiplex Cable |
|---|---|---|
| Operating Voltage Rating | 5 kV, 15 kV, 25 kV, or 35 kV Phase-to-Phase | 600 Volts Phase-to-Phase (120/240V, 208Y/120V) |
| Governing Standards | ANSI/ICEA S-94-649, AEIC CS8, ASTM B231 | ANSI/ICEA S-105-692, UL 854 (USE-2), ASTM B800 |
| Conductor Core | Aluminum 1350-H19 (Compressed/Compact) | Aluminum 1350-H19 or AA-8000 Compact |
| Primary Dielectric | TR-XLPE (Tree-Retardant) or EPR (175 to 345 mils) | Heavy-Wall Direct Burial XLPE (60 to 95 mils) |
| Electric Stress Shielding | Inner Extruded Semicon + Outer Strippable Semicon | None Required (Electrostatic stress negligible <1kV) |
| Neutral Architecture | Concentric Bare Copper Wires (100% or 1/3 Sizing) | Twisted Bare or Insulated Aluminum Conductor |
| Protective Jacketing | Extruded Encapsulating or Insulating LLDPE Jacket | Self-Jacketed XLPE Phase Insulation |
| Termination Interface | IEEE 386 200A/600A Separable Elbow Connectors | Mechanical Screw Set Terminals / Bimetallic Lugs |
| Primary Failure Mechanism | Water Treeing & High-Voltage Electric Breakdown | Mechanical Stone Puncture & Insulation Chafing |
Table 3: Secondary 600V Triplex URD Direct Burial Industry Code Words and Specifications
| Industry Code Word | Phase Conductor Size (AWG / kcmil) | Phase Insulation Thickness (mils / mm) | Neutral Conductor Size (AWG / kcmil) | Assembly Outside Diameter (mm) | Approx. Net Weight (kg/km) | Direct Burial Ampacity (90°C, Earth 20°C) |
|---|---|---|---|---|---|---|
| Brennan | 4 x 2 AWG Al | 60 mil / 1.52 mm | 4 AWG Al (Reduced) | 22.1 mm | 340 kg/km | 150 A |
| Costilla | 2 x 1/0 AWG Al | 80 mil / 2.03 mm | 2 AWG Al (Reduced) | 28.5 mm | 535 kg/km | 200 A |
| Erskine | 2 x 2/0 AWG Al | 80 mil / 2.03 mm | 1 AWG Al (Reduced) | 31.2 mm | 645 kg/km | 225 A |
| Monmouth | 2 x 4/0 AWG Al | 80 mil / 2.03 mm | 2/0 AWG Al (Reduced) | 37.8 mm | 975 kg/km | 305 A |
| Pratt | 2 x 250 kcmil Al | 95 mil / 2.41 mm | 3/0 AWG Al (Reduced) | 42.1 mm | 1,180 kg/km | 335 A |
| Sweetbriar | 2 x 350 kcmil Al | 95 mil / 2.41 mm | 4/0 AWG Al (Reduced) | 48.5 mm | 1,590 kg/km | 405 A |
| Wesleyan | 2 x 500 kcmil Al | 95 mil / 2.41 mm | 350 kcmil Al (Reduced) | 56.4 mm | 2,210 kg/km | 495 A |
Trenching, Pulling Physics, and Termination Best Practices
Achieving high operational reliability in URD systems depends as much on civil trenching and mechanical installation practices as on factory cable quality.
Trench Depth and Separation Rules
Per National Electrical Safety Code (NESC) Section 35 and NEC Table 300.5: - Primary URD Cables: Must be buried at a minimum depth of 30 to 36 inches (760 to 915 mm) below final finished grade. Where vehicular traffic is anticipated, 36 to 48 inches is standard. - Secondary URD Cables: Require a minimum burial depth of 24 inches (610 mm). - Random Separation in Joint Trenches: When primary electric cables share a common trench with telecommunication lines (such as fiber optic conduits or telephone pairs), NESC Rule 354 permits joint trenching provided the primary cable has a continuous metallic concentric neutral grounded at every transformer and junction enclosure.
Thermal Backfill and Soil Runaway Prevention
Cables buried directly in soil dissipate conductor I^2R resistive heat and dielectric losses radially into the surrounding earth. If the surrounding soil has a high thermal resistivity (RHO > 120 K-cm/W) or dries out completely during hot summer peak loads, a thermal runaway condition can occur: heat accumulation drives moisture away from the cable surface, dramatically increasing local soil thermal resistivity. The cable temperature escalates past the 90°C design limit, accelerating insulation aging and leading to premature dielectric breakdown. To eliminate this hazard, utilities embed URD cables in a 6-inch envelope of compacted sand or fluidized thermal backfill (FTB) with a guaranteed maximum thermal resistivity of 70 to 85 K-cm/W.
Conductor Pulling Mechanics in Ducts
When installing URD cables in PVC or HDPE duct runs, engineers must calculate maximum pulling tension (T) and sidewall bearing pressure (SWBP) at conduit bends using the formula: SWBP = T / R Where T is the pulling tension at the bend exit (lbs or N) and R is the inside radius of the bend (ft or m). For TR-XLPE primary cables, SWBP must never exceed 500 lbs/ft (7.3 kN/m) to prevent physical deformation of the outer jacket, concentric neutral displacement, or permanent semiconductive shield indentation. To maintain safe tension limits, contractors employ pre-lubricated conduits and specialized underground line fittings & hardware including calibrated pulling eyes and breakaway swivels.
Pad-Mounted Transformer Terminations
At transformer enclosures, primary URD cables terminate onto standard 200-amp loadbreak or 600-amp deadbreak high-voltage bushings complying with IEEE 386. Cable jointers must meticulously prepare the cable core: 1. Strip the outer jacket cleanly without scoring the copper concentric neutral wires. 2. Form the concentric neutral wires into a compact pigtail, crimp with a heavy-duty grounding terminal, and bond securely to the transformer ground bus. 3. Remove the strippable semiconductive insulation shield using dedicated radial stripping tools, maintaining strict transition bevel dimensions. 4. Clean the exposed TR-XLPE insulation surface with approved high-dielectric solvent wipes, apply silicone lubricant, and press the IEEE 386 elbow connector firmly into place. 5. On the low-voltage secondary side, terminate the aluminum secondary conductors using heavy-duty bimetallic compression cable lugs pre-filled with oxide-inhibiting compound, preventing galvanic corrosion between aluminum cable strands and copper/bronze transformer spade pads.
Quality Assurance, Factory Testing, and SiTong Cable Capabilities
Zhengzhou Sitong Cable Co., Ltd. (SiTong Cable) manufactures primary concentric neutral URD cables and secondary 600V multiplex assemblies under an ISO 9001 and ISO 14001 quality management framework, delivering fully certified products to electric utilities, EPC power contractors, and industrial distributors worldwide.
Advanced CCV Manufacturing Infrastructure
Primary URD cables are produced on computerized, high-speed triple-extrusion Continuous Vulcanization (CCV) lines. The conductor screen, TR-XLPE insulation compound, and strippable outer insulation screen are fed simultaneously through a single multi-channel extrusion head into a sealed catenary tube pressurized with dry nitrogen gas. Unlike obsolete steam-vulcanization processes, dry-curing completely eliminates micro-void moisture contamination within the dielectric matrix, providing flawless cross-linking uniformity and structural roundness verified by continuous online ultrasonic wall-thickness monitors.
Strict 100% Routine Factory Testing
Every production master reel of primary URD cable undergoes stringent routine testing in shielded high-voltage test bays prior to shipment: - 100% Partial Discharge Testing: Evaluated per ICEA S-94-649 and AEIC CS8 up to 200% of rated phase-to-ground voltage (2.0 U0). SiTong primary cables guarantee a maximum discharge level of less than 5 picocoulombs (pC), well below the international allowable limit. - AC High-Voltage Withstand Test: Conducted at 34 kV AC for 5 minutes on 15kV cables, verifying zero insulation puncture or dielectric breakdown. - Conductor Resistance and Dielectric Geometry Checks: Digital resistance bridges verify full ASTM B231 conductivity, and micro-optical measuring projectors verify concentricity and shield strip-force tension.
Frequently Asked Questions (FAQ)
1. Why is TR-XLPE preferred over standard XLPE for direct-buried primary URD cables?
Standard cross-linked polyethylene (XLPE) exhibits exceptional electrical properties in dry environments, but when exposed to moisture under continuous alternating-current electric field stress (the typical environment of directly buried cables or wet underground conduits), micro-voids in the insulation develop microscopic branched channels known as electrochemical "water trees." Over 5 to 15 years of operation, water trees grow until electrical stress initiates an electrical tree, causing sudden dielectric puncture. Tree-Retardant XLPE (TR-XLPE) contains specialized molecular stabilizing additives that trap mobile electrons and inhibit tree initiation, extending underground cable operational lifespans beyond 40 years without significant degradation.
2. How do distribution engineers choose between 100% full neutral and 1/3 neutral for primary URD?
The choice depends entirely on whether the circuit operates as a single-phase loop or a balanced three-phase distribution feeder. In single-phase residential loops, the entire phase current returns to the source through the concentric neutral; therefore, a 100% full neutral (matching the conductivity of the phase conductor) is strictly mandatory to prevent neutral conductor overheating and hazardous ground potential rise. In balanced three-phase circuits, phase return currents cancel out at the neutral point; a 1/3 neutral is selected because it saves substantial copper weight and capital cost while remaining fully sized to safely carry unbalanced currents and clear short-circuit phase-to-ground faults.
3. What causes concentric neutral wire corrosion, and how does a jacketed cable solve it?
In early unjacketed URD designs, bare copper neutral wires laid directly against the soil. In agricultural or industrial soils rich in chlorides, sulfates, and fertilizers, aggressive electrochemical corrosion dissolved the copper wires over time, creating discontinuous neutrals, phase voltage imbalances, and severe electric shock hazards at transformer cabinets. In addition, stray DC currents from cathodic protection systems accelerated galvanic corrosion. Modern jacketed primary URD cables encapsulate the concentric neutral beneath an impermeable Linear Low-Density Polyethylene (LLDPE) jacket, permanently isolating the copper from chemical attack and mechanical soil abrasion.
4. What are the installation advantages of Secondary URD Triplex compared to pulling separate conductors into conduit?
Secondary URD Triplex cables feature factory-twisted assembly where two insulated phase conductors are spiraled mechanically around the neutral conductor. This provides three major engineering advantages: first, pulling a factory-multiplexed assembly into a trench or duct cuts field labor time by more than 60% compared to handling individual spools; second, the factory twist cancels inductive reactance, reducing voltage drop along long residential service runs; third, the heavy-wall XLPE insulation is engineered specifically for direct-burial stone impingement resistance, allowing direct burial without requiring continuous rigid PVC conduit.
Conclusion and Engineering Resources
Underground Residential Distribution cables are the critical conduit delivering reliable, storm-hardened, and visually clean electricity to modern communities. Specifying the correct combination of TR-XLPE primary concentric neutral loop cables and heavy-wall secondary multiplex direct-burial cables ensures that underground distribution networks operate safely, efficiently, and maintenance-free for decades.
For technical data sheets, custom stranding configurations, and international project bidding support: